Wardoyo, Eustachius Hagni and Alit, Ida Bagus and Nasrul, Monalisa and Yudhanto, Didit and Fathana, Prima Belia and Saptaningtyas, Rini Srikus (2021) Physical Measurement Analysis in Pre-Utility Covid-19 Isolation Room: A Case Study Universitas Mataram Teaching Hospital. The Indonesian Journal of Infectious Diseases, 7 (2). ISSN 2354-6077
|
Text
LampB4-physical-measurement-analysis-in-pre-uti-vol7no2 2021.pdf Download (360kB) | Preview |
Abstract
Background: Negative pressure room is recommended for the treatment of COVID-19 patients. Aim this study to describe physical measurement analysis of isolation room Universitas Mataram Teaching Hospital. Methods: Newly developed negative pressure isolation room was physical measure using following instruments: anemometer, moisture meter, hygrometer and pressure gauge. Results: This study showed physical measurement as follow: 1) ACH (air change per hour) 23.3 / hour [minimum: 12 + ACH]; 2) the difference in pressure gradient between the inpatient room and anteroom-30 Pa [minimum-15 Pa]; 3) the mean of air temperature 24.8°C [21-24]; 4) air humidity 58% [maximum 65%] and 5) concrete moisture 22.45%. Conclusion: The COVID-19 isolation room at the Universitas Mataram Teaching Hospital meets the standard criteria
Item Type: | Article |
---|---|
Keywords (Kata Kunci): | Negative Pressure Isolation Rooms (NPIRs); COVID-19; Physical Measurement Analysis |
Subjects: | R Medicine > RZ Other systems of medicine |
Divisions: | Fakultas Kedokteran |