Physical Measurement Analysis in Pre-Utility Covid-19 Isolation Room: A Case Study Universitas Mataram Teaching Hospital

Wardoyo, Eustachius Hagni and Alit, Ida Bagus and Nasrul, Monalisa and Yudhanto, Didit and Fathana, Prima Belia and Saptaningtyas, Rini Srikus (2021) Physical Measurement Analysis in Pre-Utility Covid-19 Isolation Room: A Case Study Universitas Mataram Teaching Hospital. The Indonesian Journal of Infectious Diseases, 7 (2). ISSN 2354-6077

[img]
Preview
Text
LampB4-physical-measurement-analysis-in-pre-uti-vol7no2 2021.pdf

Download (360kB) | Preview
Official URL: https://www.ijid-rspisuliantisaroso.co.id/index.ph...

Abstract

Background: Negative pressure room is recommended for the treatment of COVID-19 patients. Aim this study to describe physical measurement analysis of isolation room Universitas Mataram Teaching Hospital. Methods: Newly developed negative pressure isolation room was physical measure using following instruments: anemometer, moisture meter, hygrometer and pressure gauge. Results: This study showed physical measurement as follow: 1) ACH (air change per hour) 23.3 / hour [minimum: 12 + ACH]; 2) the difference in pressure gradient between the inpatient room and anteroom-30 Pa [minimum-15 Pa]; 3) the mean of air temperature 24.8°C [21-24]; 4) air humidity 58% [maximum 65%] and 5) concrete moisture 22.45%. Conclusion: The COVID-19 isolation room at the Universitas Mataram Teaching Hospital meets the standard criteria

Item Type: Article
Keywords (Kata Kunci): Negative Pressure Isolation Rooms (NPIRs); COVID-19; Physical Measurement Analysis
Subjects: R Medicine > RZ Other systems of medicine
Divisions: Fakultas Kedokteran
Depositing User: Dr Eustachius Hagni Wardoyo
Date Deposited: 17 Apr 2023 02:57
Last Modified: 17 Apr 2023 02:57
URI: http://eprints.unram.ac.id/id/eprint/36668